Problem Symptoms and
Troubleshooting Checks
If you have this problem: Do this:
Inverter Indicator Light does not turn ON. Verify DC voltage at the inverter.
Inverter Indicator Light is ON but the AC load
will not operate.
Check and reset GFCI receptacle or circuit
breakers. Verify AC wiring. Try a different load
such as a trouble light.
Low Battery Indicator Light is ON when AC load
is applied.
Check battery connections and condition.
Recharge battery if voltage is less than 22.0
VDC (
44 VDC
for the RE48-4500
). Low battery
warning is 22 VDC and Inverter Shutdown is 21
VDC (
44 VDC and 42 VDC
for the RE48-4500
respectively
).
Check to see if Charger is enabled in RE-ICC
Settings Menu. Check alarm status on Charger.
Over Temperature Indicator Light is RED. Verify fan operation. Remove obstructions from
air intake vents and exhaust fan.
Inverter Light Turns RED when AC load is
applied.
Verify AC load is within the inverter’s rated
capacity. Remove excessive loads.
DC fuse blows when connecting DC input
cables.
Check for reverse polarity (Positive and negative
DC cables reversed.)
AC loads do not seem to be fully energized
when operating from inverter power.
Check AC output voltage at AC Output
Terminals. Check for overheated DC or AC
wiring. Verify AC load specifications are not
exceeded.
Unit does not operate and a “burnt wire” smell
emits from inverter/charger.
Disconnect AC loads and DC Source
immediately. Unit may require service, contact
Vanner service department.