Charge
Controller #1
Charge
Controller #2
100A
100A
300A
1A
GFDI
DC Control and Distribution Wiring
Solar Array
Junction Box
Battery Bank
INCORPORATED
RE-4500
AC Power Inverter System
MULTI-MODE ALTERNATIVE ENERGY INVERTER
U
L1
L1
L2
N
N
L2
GND
AC INAC OUT
GND
DC Conduit
Warning
It is important to disconnect ALL DC sources to avoid electric
shock!
DC Voltage is extremely dangerous and contact with DC Currents
can lead to injury, damage to property, and death!
Use the DC disconnect to insure that ALL potentials are disabled.
1.
Route the DC power wiring and AC output wiring with as
much physical separation as possible from low voltage
wiring such as audio and video signal wires.
2.
Route the DC positive and negative cables as close
together as possible and use cable ties to keep them
together. This reduces electromagnetic radiation that could
interfere with sensitive electronics.
3.
If passing through steel or other ferrous metal walls, the
DC input cables need to pass through the same hole to
prevent causing a transformer effect. If two holes are
F 5 Figure 3-5: DC Wiring Diagram