Start-up and Test Procedure
After the inverter has been properly mounted with sufficient
ventilation, verify the following:
1.
DC cables have been connected to the inverter and to the
DC Disconnect
2.
DC cable polarity is correct.
3.
The DC Disconnect is still in the OFF position (no voltage
present at output of the Disconnect)
4.
AC Disconnect is in the OFF position (no voltage present
on the output of the Disconnect).
5.
AC wiring has been completed
6.
AC phase and connections are correct
7.
All remote connections have been checked.
The Start-up and Testing procedures can now be performed.
Warning
These procedures are to be performed only by a QUALIFIED
INSTALLER.
Inverter Start-up and Testing
1.
Place the Inverter ON/OFF switch in the OFF position.
2.
Verify that any external AC output circuit breakers are
reset.
3.
Connect the DC source via the code required disconnect to
the Inverter.
4.
With a Voltmeter, verify that 24VDC is present at the
Inverter DC IN terminals.
5.
Verify that there is no voltage present on the inverter AC
output terminals (between L1 and Neutral).
6.
Connect a 120 Volt 75 watt trouble light (or other suitable
load) to the inverter AC output (between L1 and neutral)
and turn on inverter via the front panel switch.